Ambient conditions
Ambient temperature +5 … +40 °C (40 ... 104 °F)
Storage temperature –20 … +70 °C (0 ... 160 °F)
Relative humidity Max. 95% (without condensation)
Ambient air pressure: 900 … 1100 hPa (mbar)
[1]
[1]If the pressure is different: Consult SICK Customer Service and perform a pressure adaption, if required.
Degree of protection IP 40, for indoor use
Allowable contamination: Degree of contamination 2
Power supply
Mains voltage:
–Electronics
–Heating
90 .. 240 VAC (multi-range power supply unit)
115 VAC or 230 VAC (optionally)
Mains frequency 47 .. 63 Hz
Power input:
–Electronics
– Detector heating
– External heating
Max. 50 VA
Max. 350 VA
Max. 300 VA
Device connector mains fuse For 115 V and 230 V: 8 A, medium time-lag,
Type 5x20 (replaceable fusible cutout)
Gas supply
Gas Quality Flow Input pressure Connec-
tion
[1]
[1]Screw connections as supplied
Instrument air
Particle size max. 1 m, oil content
max. 0.1 mg/m
3
, pressure dew point
max. –40 °C.
1000 l/h
400 ± 20 kPa
(4 ± 0.2 bar)
G 1/8"
Fuel gas H
2
> 5.0 60 ml/min.
300 ± 20 kPa
(3 ± 0.2 bar)
Combustion air
– Measuring range > 500 mgC/m
3
:
instrument air
– Measuring range <= 500 mgC/m
3
:
Internal catalyst (option)
– Measuring range <= 500 mgC/m
3
:
External catalyst
20 ml/min.
Zero gas Catalyst or external 250 l/h
Reference gas
– Recommendation: Propane in syn-
thetic air.
– Concentration: Approx. 75% of full
scale reading.
300 l/h